Product Specifications

Model PT-404 PT-406 PT-408 PT-412
Connection Type Screwed Screwed Screwed Screwed
Maximum Allowable Pressure 150 psig (10 barg) 150 psig (10 barg) 150 psig (10 barg) 150 psig (10 barg)
Maximum Allowable Temperature 650°F (343 °C) 650°F (343 °C) 650°F (343 °C) 650°F (343 °C)
Body Material Fabricated Steel 150 psi ASME Sec. VIII Design “U” Stamped Fabricated Steel 150 psi ASME Sec. VIII Design “U” Stamped Fabricated Steel 150 psi ASME Sec. VIII Design “U” Stamped Fabricated Steel 150 psi ASME Sec. VIII Design “U” Stamped
Mechanism Material Stainless Steel with Inconel X-750 Spring Stainless Steel with Inconel X-750 Spring Stainless Steel with Inconel X-750 Spring Stainless Steel with Inconel X-750 Spring
Maximum Operating Pressure 125 psig (9 barg) 125 psig (9 barg) 125 psig (9 barg) 125 psig (9 barg)
Capacity Range 3,600 lb/hr (1633 kg/hr) 5,500 lb/hr (2495 kg/hr) 7,400 lb/hr (3,357 kg/hr) 12,200 lb/hr (5,534 kg/hr)

Vertical Pump Trap – PT-400 Series

PT-400 Series Vertical Pump Traps are a low-maintenance, non-electric solution for moving condensate or other liquids from low points, low pressures, or vacuum spaces to an area of higher elevation or pressure. Condensate can be returned at temperatures well above the 200˚F (93˚C) limit of conventional electric condensate pumps without leaking seals or cavitation problems.

Features

  • Economical non-electric operation
  • No leaking seals, impeller or motor problems means lower maintenance
  • Lower installation costs
  • Standard unit is intrinsically safe—explosion-proof
  • ASME code-stamped carbon steel body vessel
  • Internals are all stainless steel for corrosion resistance and long life
  • Springs are made from long-lasting Inconel X-750
  • All valuable Btu’s are captured and returned to the system
  • Can be used in flooded pits without fear of electrocution or circuit breaker defaults
  • Seats can be replaced or cleaned without removing the mechanism assembly

TYPICAL APPLICATIONS

  • Low-pressure heating systems
  • Process heat exchanger or coils with modulating steam control
  • Remote installations (tracing, tank farms, or remote coils)
  • Systems under vacuum
  • Hazardous (explosion-proof) areas
  • Caustic environments
  • Sumps or submersed areas
  • Reboilers
  • Flash tanks