ERS-LC Electric Steam Humidifier Launch Materials | Armstrong | Americas
Product image of ERS-LC Humidifier
ERS-LC Electric Steam Humidifier

August 1, 2023

Dear Armstrong Sales Representative,

Armstrong is excited to announce the release of the ERS-LC resistive humidifier. This is a great new addition to Armstrong Humidification. This complements our existing product line and competitive growing electric humidifier market. Visit the dedicated product launch webpage on your Armstrong user portal for detailed sales and marketing information that will help you promote this new product line.

The Primary target for the ERS-LC is the institutional market, specifically applications with low capacities or minimal space for installation and service. There could also be a play in some small industrial applications.

The ERS-LC, although new to the US market is a tested and proven product in our European market and brings us excellent opportunity to fill in market gaps we would typically not have.

If you have questions, please contact the Armstrong Humidification Department for more details.

Brian Stout
Armstrong International Humidification

Features and Benefits

  • Capacities ranging from 7 to 75 lb/hr.
    Broad spectrum of capacities to cover many applications.
  • Accepts all common control signals.
    Capable to excepting 0-10Vdc, 4-20mA, and direct control from BMS system.
  • Redundant over temperature protection.
    Two separate temperature controls monitor for overtemp conditions to protect the unit and sensitive material around humidifier.
  • Signal accuracy of +/-2%.
    Maintains humidity control within 2% of the incoming control signal.
  • Self-cleaning Incoloy elements.
    Incoloy elements are used for improved scale shedding, increasing element life.
  • Maintenance and alert prompts on display.
    LCD display provides maintenance reminders and alerts on a programmable schedule.
  • Compact design.
    ERS-LC can be placed in tight control rooms or above ceilings. ERS-LC only requires two side access for maintenance and inspection.

Download ERS-LC Features and Benefits Chart

Target Markets

The target market for the ERS-LC is low steam demand applications, and areas to be humidified with limited available space for the humidifier.

Target Industries:

  • Healthcare
  • Labs
  • Office spaces

Specific target applications include:

  • Tight mechanical spaces
  • Test cells
  • Operating rooms

Download ERS-LC Target Markets Document

Specification

Category: Humidifier
Type: Electric
Model: ERS-LC

  1. Armstrong ERS-LC humidifier for the production of sterile steam.
  2. Galvanized zinc, epoxy painted cabinet shall have separate water and electrical compartments for safety. Secure removable door panels on 3 sides, providing easy access for installation and maintenance.
  3. Humidifier shall generate steam from potable water (water hardness min 50 ppm/max 400 ppm with water level with electrode) and DI or RO water (water level with float). For operation with softened or partly softened water please contact your Armstrong representative.
  4. Draining settings shall be adjustable depending on the quality of supply water to optimize energy consumption.
  5. Production from 3 to 35 kg/h (7 lb/h to 75 lb/h) of steam.
  6. Humidifier shall accept fully common modulating signal ON/OFF or proportional. The microprocessor regulates proper filling and draining, can limit capacity at 50% of nominal output and modulates capacity between 0% to 100%. ± 2% signal accuracy.
  7. Humidifier is interoperable through native modbus communication protocol.
  8. Digital display and keypad on the front panel shall indicate all functions of the humidifier.
  9. Humidifier shall have a tank in permanent stainless steel with passivated welds.
  10. Humidifier shall have a tilting tank with intermediary position to easily collect limescale and minerals.
  11. Humidifier shall have self-cleaning heating elements in INCOLOY 825.
  12. Humidifier shall have two power lamps on front of the unit to indicate power and steam production.
  13. Humidifier shall have a programmable maintenance schedule timer: 300 hours in standard, adjustable from 100 to 20 000 hours.
  14. Humidifier shall have drain solenoid valve with a large orifice for easy limescale evacuation.
  15. Humidifier shall have anti-foaming automatic drains.
  16. For large duct or short absorption distance, humidifiers shall be compatible with Humidipack and ExpressPack.
  17. End-of-season auto drain of the cylinder after period of inactivity: 3 days in standard but adjustable from 12 hours to 7 days.
  18. Water supply pressure to humidifier shall range between 2 to 6 bar (29 psi to 87 psi), inlet valve shall include a flow restrictor and a built-in strainer.
  19. Supplied with a flexible limescale collecting bag.
  20. Capacity to be linked with Armstrong sensor and humidistat for fully automatic control.
  21. Shall allow to maintain the temperature of the water inside the tank between 65°C (149°F) and 75°C (167°F) (antilegionella).
  22. Humidifier shall have temperature sensor immersed in the evaporation chamber which prevents over-temperature.
  23. High flow cooling fan will be incorporated inside the electrical compartment.
  24. The humidifier should have the following options available:
    1. BMS with Bacnet communication.
    2. BMS with Modbus communication.

Download ERS-LC Specification

Questions and Answers

What is the ERS-LC?

The ERS-LC is a low capacity, compact, resistive humidifier. The ERS-LC can produce from 7-75 lb/hr steam capacities. It is available in most common voltages and is compatible with potable, softened, and RO/DI grade water.

What Controls are available for the ERS-LC?

Keeping with industrial standard the ERS-LC can except 0-10v signal as well as 4-20mA signals. The main board is selectable Modbus or BacNet native.

Can the ERS-LC be installed in an occupied space?

Yes, with its attractive housing and only hanging 10 inches off the wall the ERS-LC works great in occupied spaces. It can be matched with a fan pack on top for area dispersion or used with a dispersion tube in the duct.

What Dispersion is available?

The ERS-LC can be used with standard “D” dispersion tubes or any of the Humidipack series for shorter absorption distances.

How is the ERS-LC Maintained?

ERS-LC does not employ Ionic Bed technology but is designed with scale shedding Incoloy heating elements that will require regular cleaning along with the tank. As is common with all humidifiers, hard water will require more frequent cleaning. Softened water will ease the cleaning process. The canister and elements are easily removed for tank cleaning and inspection or complete tank replacement. The ERS-LC only requires access on two sides for maintenance, with lift off panels reducing the amount of space required to access the humidifier.