Model | Flow Capacity at 20 psig (1.38 barg) drop | Hot Water Outlet Connection Size |
Z358-20 | 15 gpm (57 lpm) | 3/4″ (20 mm) |
Z358-40 | 31 gpm (117 lpm) | 1-1/4″ (32 mm) |
Model Z358 is a thermostatic mixing valve (TMV) available in two flow capacities and suitable for installation at or near a point of use for tepid water supply to a single, combination or group of emergency fixtures in accordance with ANSI standard Z358.1-2009.
The unique constant cold-water flow feature allows inlet hot water supply to be set within a prescribed range, which limits the potential outlet temperature to a safe maximum. The valve also features a single temperature locking feature and a thermal shutdown feature that protects users from accidental scald risks in the case of an interruption to cold water supply.